Pouring Of Transformer Component
HY 8125 Epoxy Casting System For 10–35 kV medium- and high-voltage indoor instrument transformers 01 Mixing Ratio 02 Application HY8125A / HY8125B is recommended for 10–35 kV medium-voltage and high-voltage indoor instrument transformers. 03 Operating Method Casting process 04...
Description
HY8125
Epoxy Casting System
For 10–35 kV medium- and high-voltage indoor instrument transformers
01 Mixing Ratio
|
Component |
Parts |
|
HY8125A Epoxy Resin |
100 pbw |
|
HY8125B Curing Agent |
100 pbw |
|
Silica Filler |
300–350 pbw |
02 Application
HY8125A / HY8125B is recommended for 10–35 kV medium-voltage and high-voltage indoor instrument transformers.
03 Operating Method
Casting process
04 Characteristics
● Extremely low initial mixed viscosity
● Excellent mechanical and electrical properties
● Adjustable filler content and crack-resistance performance
05 Physical Properties of Single Components
HY8125A Modified Liquid Epoxy Resin
|
Parameter |
Value |
|
Viscosity at 25 °C, mPa·s [ISO 2555] |
3000–6000 |
|
Non-volatile content, wt% |
100 |
|
Density at 25 °C, g/cm³ [ISO 1675] |
1.10–1.20 |
|
Shelf life at 25 °C (sealed container), months |
12 |
|
Note: To prevent moisture absorption, store the epoxy resin in sealed containers at ambient temperature (approx. 6–35 °C). Typical values shall not be regarded as product specifications. |
|
YH8125B Liquid Modified Anhydride Curing Agent
|
Parameter |
Value |
|
Viscosity at 25 °C, mPa·s [ISO 2555] |
400–800 |
|
Density at 25 °C, g/cm³ [ISO 1675] |
1.15–1.25 |
|
Vapour pressure at 20 °C, Pa |
< 1 |
|
Shelf life at 25 °C (sealed container), months |
12 |
|
Note: Anhydride curing agents are highly moisture-sensitive. Excessive moisture may alter the reactivity of the system and consequently degrade final product performance. Store anhydride curing agents in sealed containers at ambient temperature (approx. 6–35 °C). Typical values shall not be regarded as product specifications. |
|
06 Process Procedure
Please contact our technical service staff for further information.
07 Processing Conditions
Please contact our technical service staff for further information. Demoulding time and post-curing cycle shall be determined according to specific product design and manufacturing process. For more details, please contact our technical service personnel.
08 Process Parameters (Guideline Values)
|
Component |
Parts |
|
HY8125A Epoxy Resin |
100 parts by weight |
|
HY8125B Curing Agent |
100 parts by weight |
|
Silica Filler |
330 parts by weight |
|
Notice: The grade and quality of the silica filler will affect process parameters such as initial mixed viscosity and reactivity. Typical values shall not be regarded as product specifications. |
|
09 Mechanical & Physical Properties (Guideline Values)
Specimen post-curing condition: 10–12 h @ 120–130 °C
Tensile Properties [ISO 527]
|
Parameter |
Value |
|
Tensile strength at 25 °C, MPa |
70–90 |
|
Elongation at break, % |
1.0–1.5 |
|
Tensile modulus E, MPa |
10 000–12 000 |
Flexural, Thermal and Electrical Properties
|
Parameter |
Value |
|
Flexural strength at 25 °C, MPa [ISO 178] |
120–140 |
|
Impact strength, kJ/m² [ISO 179] |
≥ 12 |
|
Coefficient of linear thermal expansion (30–80 °C), ppm/K |
35–40 |
|
Thermal conductivity, W/(m·K) |
0.8–1.0 |
|
Water absorption (10 days @ 23 °C), % [ISO 62] |
0.1–0.2 |
|
Dielectric strength at 25 °C, kV/mm [IEC 60243-1] |
30–35 |
|
Volume resistivity at 25 °C, Ω·cm [IEC 60093] |
10¹³–10¹⁵ |
|
Dielectric constant ε′ [IEC 60250] |
4.0–5.0 |
|
Dielectric loss tan δ at 50 Hz, 25 °C [IEC 60250] |
< 0.025 |
10 Industrial Hygiene
Comply with industrial hygiene standards during handling and processing. Refer to the corresponding Safety Data Sheet and Hygiene Protection Measures for Plastic Products Handling for additional information.
11 Operational Protection Measures
Workplace Safety
Protective clothing, gloves, arm protection, safety goggles / safety glasses and a dust-proof respirator are required when skin contact is possible.
Skin Protection
● Apply barrier cream on exposed skin before work.
● Apply repairing or nourishing cream after washing hands.
● For skin contamination: wipe off excess material with absorbent paper, rinse with warm water and alkali-free soap, then dry with disposable towels. Do NOT use solvents.
Workshop Environment
Cover workbenches and chairs with light-coloured paper; use disposable beakers and similar utensils. Absorb spills with sawdust or waste cotton rags and collect in plastic woven baskets.
Ventilation
Workshop ventilation: 3–5 air changes per hour. Provide a local exhaust fan at workstations. Operators shall avoid vapour inhalation.
12 First-Aid Measures
In case of eye contact with resin, curing agent or casting compound: flush the eyes immediately with plenty of clean running water for 10–15 minutes and seek medical attention. For skin splashes or contamination: wipe off the material first and rinse the affected area with running water as described above. Seek medical help in case of severe irritation or burns. Remove contaminated clothing promptly. If discomfort occurs from vapour inhalation, move the person to fresh air immediately. Seek medical advice if in doubt.
Disclaimer
The data in this datasheet are typical laboratory guideline values and shall not be regarded as product specifications or guaranteed values. Actual performance depends on formulation, filler grade, process conditions and part design. Please consult the corresponding Safety Data Sheet (SDS) before use. Zhejiang Heyi Chemical Co., Ltd reserves the right to revise the technical information of its products.